Fire Alarm System > Conventional
Conventional Fire Control Panel – two signal loops
Model: FS4000/2
Code: #02350
Brand: UniPOS
328.93
In Stock

Product Description

Fire control panel FS4000 is designed to operate with conventional automatic fire detectors and manual call points. The panel has outputs provided for external executive devices.

The unit is produced in four versions:
2 fire alarm lines – FS4000/2
4 fire alarm lines – FS4000/4
6 fire alarm lines – FS4000/6
8 fire alarm lines – FS4000/8

Technical features

Fire alarm lines:
– Maximum number of fire detectors in a line: 32
– Connecting line: two-wire
– Maximum resistance of a line: 100 Ω

Current thresholds for:
– Fault condition: 0 – 6 mA
– Duty mode: 6 – 16 mA
– Fire condition: 16 – 80 mA
– Short circuit: > 80 mA

Monitored outputs for fire condition:
– Number: 2 pcs
– Type: potential, relay with independent control
– Electrical characteristics: (19-27.5)V DC/1A

Relay outputs for fire condition:
– Number: 2 pcs
– Type: potential-free,1 switching, 1 NO
– Electrical characteristics: 3А/125V AC, 3A/30V DC

Relay output for fault condition:
– Number: 1 pcs
– Type: potential-free, switching
– Electrical characteristics: 3А/125V AC, 3A/30V DC

Relay output for fault condition:
– Number: 1 pcs
– Type: none-monitored type activated on short-circuit (from potential free contact)
– Electrical characteristics: 5 VDC on normal open state / 0 VDC in activation mode
Performance:
– Control over fire alarm lines and controllable outputs for fault conditions (short circuit and interruption) and automatic reset.
– Detection of removed fire detector and automatic reset.
– Identification of manual call points.
– LED indication for alarm state and emergency.
– Delay of outputs for fire condition with time period of 1, 2, 3, 4, 5, 6 or 7 minutes after fire condition is registered.
– Option for ‘LOGICAL AND’ realization of two fire alarm lines.
– Duty Mode condition with direct activation of Fire Condition 2nd Stage ” for two fire alarm lines.
– Status Indication of the device for data transmission RS485.
– Option for switching on/off interface RS485 communication.
– Built-in sounder for fire condition – one tonal, continuous, can be switched off.
– Built-in sounder for fault condition – one tonal, discontinuous, can be switched off.
– Test mode for fire alarm lines.
– Disabling fire alarm lines.
– Disabling outputs for fire condition.
– Expanding the options by means of extra relay outputs for fire condition for each line and built-in RS485 for operation in a local network.
– Input for remote Reset fires operation;

Indications of registered events:
– Light indication: LED
– Sound: Built-in buzzer

Power supply:
– Voltage: (100-240)V AC
– Frequency: 50/60 Hz

Backup batteries:
– Battery type: lead, gel electrolyte
– Number of batteries: 2 pcs
– Nominal voltage of the backup battery: 12V
– Nominal capacity C20: (7,0) Ah
– Charge voltage: 28V DC

Operation in Duty mode upon interruption in main power supply:
Lines – 24V / 1,2Ah – 24V / 4,5Ah – 24V / 7,0Ah
2 lines – 32 h – 120 h – 180 h
4 lines – 24 h – 98 h – 140 h
6 lines – 20 h – 80 h – 110 h
8 lines – 16 h – 68 h – 90 h

Consumption on backup batteries supply:
– Configuration of 2 lines: < 35 mA at 24V DC
– Configuration of 4 lines: < 45 mA at 24V DC
– Configuration of 6 lines: < 55 mA at 24V DC
– Configuration of 8 lines: < 65 mA at 24V DC

Power supply to external devices:
– Voltage: (19-27)V DC
– Maximum current value (including current of contr.outputs): 1,2A

Fuses:
– Main supply 230V: 4.0 A
– Backup battery: 6.0 A
– Power supply to external devices: 1.85 A automatic
– Monitored outputs: 1.1 A automatic

Dimension: 304mm x 222mm x 94mm
Weight (backup batteries not included): 0.98 kg


Recommended
Conventional Optical Smoke Fire Detector

Conventional Optical Smoke Fire Detector

FD8030
#02351
25.86
In Stock
Bases series 8000

Bases series 8000

DB8000
#02352
8.59
In Stock
Conventional indoor sounder

Conventional indoor sounder

8204CS
#02314
37.86
In Stock
Conventional Manual Call Point

Conventional Manual Call Point

FD3050
#02353
29.62
In Stock
DB 7100 Detector Base

DB 7100 Detector Base

DB7100
#01906
9.49
In Stock
Addressable smoke detector FD7130

Addressable smoke detector FD7130

FD7130
#01905
58.40
In Stock
Manual call point FD7150

Manual call point FD7150

FD7150
#01907
70.87
In Stock
Input-Output device FD7203 – 1 input / 1 output

Input-Output device FD7203 – 1 input / 1 output

FD7203IO
#01909
101.34
In Stock
FD7204D Addressable Sounder

FD7204D Addressable Sounder

FD7204D
#01908
102.95
In Stock
Interactive Fire Control Panel IFS7002 –  four signal loops

Interactive Fire Control Panel IFS7002 – four signal loops

IFS7002‑4
#02219
3734.97
Subject To Order
Fire Resistant Cables 1x2x0.8mm +0.8mm-100m

Fire Resistant Cables 1x2x0.8mm +0.8mm-100m

JE‑H(St)H Bd FE180 PH120 1x2x0.8mm +0.8mm‑100m
#02229
132.88
In Stock
Fire Alarm Cables 1x2x0.8 mm+0.5 mm-500m

Fire Alarm Cables 1x2x0.8 mm+0.5 mm-500m

J‑Y(St)Y 1x2x0.8 mm+0.5 mm‑500m
#02227
388.82
In Stock
Fire Resistant Cables 1x2x0.8mm +0.8mm-500m

Fire Resistant Cables 1x2x0.8mm +0.8mm-500m

JE‑H(St)H Bd FE180 PH120 1x2x0.8mm +0.8mm‑500m
#02228
631.56
In Stock